Specifications include, but are not limited to: Job will include a dry inspection, dry cleanout, and repair to Louisiana State Penitentiary's million gallon tank. * tank type: GST- ground storage tank * capacity: 1,000,000 * diameter: 92' * height: 20' * construction type: welded * inspection of tank will be for compliance with the following codes and standards: AWWA, EPA, NFPA 22, NFPA 25, OSHA Includes Dry Cleanout: * clean out / remove sediment and debris from tank floor tank will be disinfected in accordance with AWWA method 3 - method 3- disinfection procedure: place 1.6 lbs of calcium hypchlorite (65% HTH) in fill line per each 50 mg gallons of water and fill the tank to approximately 5% of it capacity. - LSP will let stand for a minimum of six(6) hours. Fill the tank with potable water to overflow level and let stand for a minimum of twenty-four (24) hours. - purge all highly chlorinated water from the drain piping - following this procedure, and subject to satisfactory bacteriological testing, by others, acceptable aesthetic quality, the remaining water may be delivered to the distribution system. REPAIR: * replace the existing liquid level indicator and install a new one, complete with a target board and float * replace and properly adjust existing liquid level indicator with new National Fire Protection Association approved liquid level indicator per attached drawing.