Specifications include, but are not limited to: The skid unit shall be delivered complete and fully operational. It shall be properly serviced, free of leaks and all mechanical adjustments made prior to delivery. The skid platform is to be ¾” copolymer polypropylene with dimensions of 48” wide and 43” long. The tank will be Lshaped leaving an area 25”X 36” for the pump motor and plumbing. The tank shall hold 70 gallons of water and meet NFPA minimum standards for design capacity, filler size, venting, and draining The foam concentrate reservoir shall hold 5 gallons of foam concentrate and also meet NFPA minimum standards The foam and water cells shall have a 2” vertical sight glass built in that shall be visible from the driver’s side of the UTV. *See the attached drawing of the tank for placement* The water tank is to be baffled the length and width of the tank The fill towers for foam and water are to be no smaller than 8” and located on the driver’s side meeting NFPA standards for venting The water and foam tanks are to be constructed out of at least ½ “ polypropylene and fully welded to the skid platform The tank shall have a storage area with 4” sides made of polypropylene and lifting points to steadily lift the entire unit with a hoist