Specifications include, but are not limited to: I. Minimum breaker requirements: A. 1200 A Breaker B. Outdoor Substation Circuit Breaker, NEMA 3R, C. Three Pole, Single Throw, Free Standing D. Dead Tank, Vacuum Circuit Breaker, E. ANSI 70 F. Continuous Current: 1200 Amps G. Impulse Withstand Voltage: 110kV BIL H. Max Short Circuit Current: 25 kA (RMS) I. Maximum Voltage: 15.5kV J. 6 CT’s 1200:5 Multi – Ratio C200 Class K. Spring Charge Motor: 120 VAC L. Close Coil: 120 VAC M. Trip Coil / Relay: 24 VDC N. 120 AC Volt Heater II. Minimum wiring and installation requirements: A. Relay panel in the breaker B. SEL 751A with 24-volt control power Microshield with 125-volt control power C. One red indicating light D. One green indicating light E. One interposing relay for the trip circuit F. One interposing relay for the close circuit G. The relay and indicating lights should be wired to the breaker H. Installation of the breaker I. Reroute existing conduits J. Reconnect existing control cables K. Modify breaker foundation L. Remove the existing breaker M. Set the new breaker N. Reconnect primary drops to the breaker