Specifications include, but are not limited to: Provide equipment, materials and labor for a new two product above ground fuel storage and dispensing system adjacent to the generator building. It consists of 2000 gallons of diesel, and 4000 gallons of gasoline storage, with metered fuel pumps connected to an electronic, key operated control system with operational software loaded on an owner supplied computer on site. It will have new electronic fuel inventory monitoring with access via the existing network. This system will have a new 75 gallon day tank connected to the diesel tank through double wall underground supply and return lines, and be operational before the old day tank is taken out of commission. 1 - 6,000 gallon above ground Dual Fuel Storage tank – split between a 4000 and 2000 gallon above ground, double wall storage tank with 2 hour fire rating 1 - Set tank hardware including vents, mechanical overfill valves, spill containment at delivery point, secondary leak indicators, steel product piping, valves and labeling 1 - Electronic inventory control system with touch screen, printer and network interface 2 - Fuel pumps with gallon registers, up to 20 GPM with automatic nozzles 1 Fuel control system, pedestal mount, electronic key operated with communication software and 50 keys 1 - 75 Gallon day tank, complete with valves, vents and overflow return system via double wall underground piping