Specifications include, but are not limited to: Weitendorf Agricultural Education Center – The existing Simplex fire alarm system shall be upgraded to EDWARDS EST3 with one-way voice communications system. 1. All the existing initiating devices will be replaced with new EDWARDS Signature Series Intelligent Addressable Devices, Smoke Detectors, Heat Detectors, Duct Smoke Detectors, Manual Pull Stations, and Sprinkler Monitoring. 2. The existing smoke detectors in the Exhibition Areas A, B & C, will be changed to Intelligent Addressable Heat Detectors 135 degree fixed temperature. 3. Replace the existing Horn-Strobes with new Speaker-Strobes or Strobes as noted on the drawings. 4. Replace the existing control panel with EDWARDS EST3 with (8) pre-recorded voice messages, audio amplifiers, microphone, audio selector switches, 4 programmable disable switches, and re-connect to the existing AES Radio Transmitter. 5. Connect the new EST3 Control Panel to the main Joliet Junior College Campus existing Fireworks Server using the existing College Network. Provide CAT6 Cable connect between the EST3 and the IT Closet located in room W1111. Include all programming of the existing Fireworks Server Workstation, including floor plan graphics, audio selector screens, and extended messages. Coordinate with the College with the screen layouts and configurations