Specifications include, but are not limited to: The Vendor shall perform load tests for certification on the existing davit bases and portable davit arms to a workload of 1,150 pounds which will be equal to a 5,000-pound load test. The suspended scaffolding davit load test will be conducted at the location identified below ONLY. The test should be equivalent to a static load of two times the working load for suspended scaffolding (swing stage) use. All testing shall perform based upon the design and in accordance with the OSHA recognized national industry standard and Chicago Municipal Code requirements for façade access. Upon notification by the Facilities Management Manager of Custodial Service, Bridget Price, the Vendor shall schedule and perform repairs and re-testing for certification on any failed davit bases and portable davit arms to a workload of 5,000 pounds which will be equal to 5,000-pound load test. The re-test should be equivalent to a static load of 2 times the working load for suspended scaffolding (swing stage) use. All re-testing shall perform based upon the design and in accordance with the OSHA recognized national industry standard and Chicago Municipal Code requirements for façade access.