Specifications include, but are not limited to: A. Install five ductless split air conditioning units to condition the new Server Room. Associated condensing units will be installed on the roof. B. Provide a room space temperature/relative humidity sensor interfaced with the existing JCI building automation system for monitoring and alarm notification. C. Modify the existing roof mounted air conditioning unit (RTU) ductwork and controls to provide conditioning for the Mezzanine Level located above the new Server Room. D. Provide a Clean Agent Fire Suppression System to protect the new Server Room. The system will include a manual release switch, an abort switch, alarm horns and strobes, and a control panel to monitor and activate the system. The control panel will be monitored by the building fire alarm system and the building automation system. E. Provide new electrical work and light fixtures as shown.