Specifications include, but are not limited to: A. Test and Balance of all HVAC systems within plus or minus ten (10) percent of the design requirements. Use test stations provided. If no test station is provided, use flow/pressure characteristics from product data. B. Minimum Data Required 1. All motors (Data to be tabulated with equipment driven by motor). a. Specified data from equipment schedule. b. Manufacturer c. HP and BHP d. Nameplate phase, voltage, FLA, RPM, and S.F. e. Actual voltage. NLA and FLA. f. Starter size, heater size and rating 2. Air moving equipment (air handling units, exhaust fans, supply fans, water source heat pumps, split system air conditioning units or heat pumps). 1) Specified data from equipment schedule. 2) Installation data 1) Manufacturer, model number and serial number. 2) Motor sheave and shaft size. 3) Fan sheave and shaft size. 4) Fan belt size and quantity. 5) Filter size, quantity and condition. 3) Test data (equipment 1000 CFM and over) 1) CFM (supply, return and outside) by duct traverse. See B.3.c. 2) Fan RPM