Specifications include, but are not limited to: 2.2. Perform a detailed survey of the entire facility to ensure all fire dampers and smoke dampers are located. Each damper shall be assigned a unique identifying number during the inspection. A sticker or identifying mark shall be placed on or near the damper with this number during inspection. A label shall be placed on the ceiling directly below the location of the damper to identify each damper location when looking up at the ceiling. The location of each damper shall be placed on the County’s drawings. 2.3. Operate all fire dampers and smoke dampers by removing and resetting the fusible link, where applicable, to verify full closure and proper operation. 2.4. Replace all fusible links that are compromised by either damage or paint. Fusible links shall be replaced with a link of the same size, temperature rating, and load rating. 2.5. Manually activate electric and pneumatic dampers to verify full closure and proper operation. 2.6. Lubricate all moving parts of fire dampers and smoke dampers. 2.7. Remove lint and dust that may impede proper operation of fire dampers and smoke dampers. 2.8. Adjust actuators as necessary to ensure proper operation of all fire dampers and smoke dampers. 2.9. Adjust and straighten tracks to ensure proper operation of all fire dampers and smoke dampers. 2.10.Replace springs as necessary to ensure proper operation of all fire dampers and smoke dampers.