Specifications include, but are not limited to: A. Acceptable control system manufacturer: 1. Johnson Controls, Inc. B. Scope includes labor and materials including but not limited to: 1. Tools and other equipment 2. Software, licenses, configurations, and database entries 3. Interfaces, wiring, tubing, labeling 4. Engineering and calculations 5. Calibration, testing, verifications, training, and other services 6. Documentation, samples, submittals 7. Permits, professional licenses, etc. 8. Other Administrative fees such as parking, shipping, handling, etc. C. Provide a complete system and be accessible via manufacturer's specific server system using a web browser interface implemented over the Owner's intranet as well as over the Internet. D. The BAS network includes but is not limited to the following: 1. Operator PCs – fixed or portable 2. Connection to existing network servers 3. Communications equipment needed to support the in-building communication BAS network 4. Intelligent and addressable elements and end devices 5. Third-party equipment interfaces 6. Other components required for a complete and working BAS 7. The BAS Network shall utilize an open architecture capable of all of the following: a. Utilizing standard Ethernet communications operating at a minimum speed of 10/100 Mb/sec. b. Connecting via BACnet/IP at the Tier 1 level in accordance with ANSI/ASHRAE Standard 135-2008. All points shall be made available for monitoring via BACnet/IP. 8. The BAS network shall support both copper and optical fiber communication media at the Tier 1 level. 9. The system shall be compatible with the owner network. Refer to owner standards for additional guidelines and information. 10. The BAS shall be fully expandable with the addition of hardware and/or software. Expansion shall not require removal of existing DDCP, sensors, actuators, or communication networks. 11. System must be of a modular design to ensure reliability and system performance. 12. All electrical work required as an integral part of this section is work of this section. 13. Provide final power connections including conduit, wire, and/or control panel disconnect switches to all control devices from appropriate electrical j-box. 14. Include the following integrated features, functions, and services: a. Operator information, alarm management, and control functions at any operator’s console without the need to purchase special software from the contractor or BAS manufacturer for those consoles b. Information management including monitoring, transmission, archiving, retrieval, and reporting functions c. Diagnostic monitoring and reporting of BAS functions d. Energy management e. Wireless Device capability