Specifications include, but are not limited to: FIRE HYDRANT 1. Hydrants shall be dry barrel type with O-ring seals, 6" MJ inlet, 5'1/4" valve opening, 2 2-1/2" nozzles, 1 4-1/2" nozzle, breakaway flange, 5-1/2' bury (unless indicated otherwise). The MJ inlet shall be supplied with one (1) set of Type I - Mechanical Joint Retainer Glands. 2. Hydrant and all interior/exterior coatings shall be in full compliance with (i.e. meet or exceed) all requirements of the latest revisions of AWWA C502. MANHOLE FRAMES AND COVERS 1. Manhole frames and covers shall have the words “MANCHESTER SEWER” cast in the cover and shall be coated with a bitumastic coating prior to delivery. 2. Frames and covers shall be in full compliance with (i.e. meet or exceed) all requirements of the last revision of ASTM A-48 (Class 30B). MECHANICAL JOINT RETAINER GLANDS & BOLTAND GASKET PACKS 1. Retainer gland shall be made of high strength ductile iron and shall provide restraint by imparting wedging action against the pipe, increasing its resistance as separation pressure increases. Each retainer gland shall include all accessories (i.e. gasket, nuts, Tbolts, etc.) necessary to completely assemble the joint. 2. Retainer gland and accessories shall be in full compliance with (i.e. meet or exceed) all requirements of the latest revisions of AWWA C111 and AWWA C153.