Specifications include, but are not limited to: Perform inspection, maintenance, support and repair services upon request for electrical power systems and equipment located at the Water Pollution Control Facility and Outdoor Sub Stations. Services shall be provided by the Contractor for all equipment, controls, components and related devices, but not limited to, as specified. All repair and/or replacement parts required to maintain the system in its original operating condition shall be of the same quality to existing. Perform NETA maintenance tests on the following switchgear: Sub 1A Two (2) 3000kva oil filled transformers. Sixteen (16) GE Low Voltage Circuit Breakers – primary current tests. Clean switchgear. Sub 2A Two (2) 3000kva oil filled transformers. Sixteen (16) GE Low Voltage Circuit Breakers – primary current tests. Clean switchgear. Transformer tests shall consist of Doble power factor, winding resistance, transformer turns ratio (at tap position), insulation resistance and oil tests to include dielectric, interfacial tension, specific gravity, acidity, color, water in oil and dissolved gasses. Low Voltage Circuit Breaker tests shall include primary current, contact and insulation resistance tests and a visual/mechanical inspection.