Specifications include, but are not limited to: Two multi user restrooms (Mens and Womens). 2. Will be pre-plumbed and pre-wired and meet all Colorado building codes. 3. Will be a minimum size of 10’ x 23’ or 230 sq. ft. 4. The Pre-cast Concrete Multi-user Flush Restroom Facility shall meet all applicable ADA accessibility and building code requirements. The facility shall also meet structural loads such as listed below, but is not limited to/or restricted by them. a. Roof Snow Load - withstand a 250 PSF snow load. b. Floor Load - withstand 400 PSF floor load. c. Wind Load - withstand the effects of 150 miles per hour (3-second gust) wind exposure. d. Additional Design Standards: 1. The building shall be an all concrete design with a minimum 3/12 roof pitch with a minimum 4” wall, 4½” roof, and 5” floor thickness.