Specifications include, but are not limited to: a. Provide full height, air filled, incoming and outgoing terminal compartments with hinged doors, separated by a steel barrier. b. Construction of unit shall be load break dead-front high side. c. Three Phase: Construction of unit shall consist of an on/off primary switch. d. Three Phase: Equip primary section with six (6) 200-amp bushing wells. e. Low voltage bushings shall be threaded stud type. f. Provisions for grounding shall be provided in both high and low voltage sections. g. Enclosure of unit shall conform to ANSI Standards for tamper resistance and coating. h. The high voltage terminations and equipment shall be dead front and conform to ANSI requirements. i. The core shall be visibly grounded to the frame by means of a flexible XO grounding strap.