Specifications include, but are not limited to: • 100% parts coverage (excluding batteries, air filters, and proactive full bank capacitor and fan replacement). • Perform temperature check on all breakers, connections, and associated controls. • Repair and/or report all high temperature areas. • Perform a complete visual inspection of the equipment including subassemblies, wiring harnesses, contacts, cables, and major components. • Check air filters for cleanliness (if applicable). • Check rectifier and inverter snubber boards for discoloration. • Check power capacitors for swelling or leaking oil (if applicable). • Check for DC capacitor vent caps that have extruded more than 1/8” (if applicable). • Record all voltage and current meter readings on the module control cabinet or the system control cabinet. • Measure and record harmonic trap filter currents (if applicable). • Check the inverter and rectifier snubbers for burned or broken wires. • Check all nuts, bolts, screws, and connectors for tightness and heat discoloration. • Check fuses on the DC capacitor deck for continuity (if applicable). • With customer approval, perform operational test of the system including unit transfer and battery discharge