Specifications include, but are not limited to: Annual preventive maintenance and inspection services for three (3) Caterpillar 3516 1875KW capacity emergency generators. Proposer is welcome to submit their company’s recommended service program in addition to City’s stated scope of work. Engine and miscellaneous equipment service to be performed on an annual basis: 1. Test safety system. 2. Inspect exhaust system, generator and controls, engine for fluid leaks, engine fan belts, and hoses. 3. Examine radiator louver operation, fuel system connections, fluid levels, and test antifreeze condition. 4. Load test batteries. 5. Service water jacket recirculation system. 6. Service battery cable connections. 7. Start engine and run under facility load; coordinate with plant personnel. 8. Take hot oil sample and provide sample to maintenance staff for analysis. 9. Clean air filters. Replace as needed. 10. Change fuel filters. 11. Change water filter, if applicable. 12. Check/add antifreeze and conditioner. 13. Clean engine and area. 14. Provide documentation of service, needed repairs and problems. 15. Disposal of any hazardous waste oil and coolant.