Specifications include, but are not limited to: A. Bidder shall refer to the following Project Specific Site and Utility Data. Bidder's design shall be suitable for operation at the conditions of service identified by this specification. B. Altitude: 935ft C. Maximum outdoor air temperature design basis: 115 degrees F D. Minimum outdoor air temperature design basis: 0 degrees F E. Control room temperature range: 68 degrees F to 75 degrees F F. Degree of outdoor pollution: Light G. Outdoor air conditions: Dust/Sand H. Maximum indoor relative humidity: 50% I. Outdoor relative humidity: 100% J. Maximum wind velocity design basis: 115 mph K. CBC Site Class: D L. CBC Risk Category: IV M. Seismic Importance Factor 1.5 N. 115kV Transmission system maximum operating voltage:126kV O. 115kV Transmission system average operating voltage: 120kV P. 115kV Transmission system minimum operating voltage: 114kV Q. 230kV Transmission system maximum operating voltage: 247kV R. 230kV Transmission system average operating voltage: 235kV S. 230kV Transmission system minimum operating voltage: 223kV T. Generator rating: 50/57.5MVA, 13.8kV nominal, 14.49kV maximum, 13.11kV minimum. U. Generator sub-transient reactance: 0.13 to 0.35 (expected possible range, not precisely known as generators will be rewound) V. Lightning Frequency: 0.25 flashes/square km/year