Specifications include, but are not limited to: Proposal is hereby made to furnish and deliver to the LADWP, care of Storekeeper, f.o.b. cars or trucks, Store 86, 14401 Saticoy Street, Van Nuys, CA 91405, in accordance with IFB Number 553, the following: Items 1 through 10 shall be a switchgear, SF6 insulated, padmounted, 38kV, 600 Amps, 25kA short circuit rating, and complies with these specifications and buy descriptions listed in Appendix A. The switchgear 3-digit model numbers are written in below. The first digit shall indicate the total number of ways where a way may be load-interrupter, fault interrupter, or bus taps. The second digit shall indicate the total number of load-interrupter switches. The third digit shall indicate the total number of fault interrupters. For example, a switchgear model 321 shall be a switchgear with a 3 way switch having 2 load interrupters and one fault interrupter. A switchgear model 523 shall be a switchgear with a 5 way switch having 2 load interrupters and 3 fault interrupters.