Specifications include, but are not limited to: 1. Piping 2. Valves 3. Each type and size of fuel oil storage tank. Indicate dimensions, weights, loads, components, and location and size of each field connection. 4. Fuel oil storage tank accessories 5. Fuel oil storage tank pumps 6. Fuel oil storage tank piping specialties 7. Leak-detection and monitoring systems, including liquid-level gage systems 8. Wiring diagrams: Power, signal, and control wiring ; Threaded pipe connection fittings on top of tank, for fill, supply, vent, sounding, and gaging, in locations and of sizes indicated. Include cast—iron plugs for shipping. Verily locations on submittal. B. Striker Plates: Inside tank, on bottom below fill, vent, sounding, gage, and other tube openings ; Locate groups of pipes parallel to each other, spaced to permit valve servicing. B. Install fittings for changes in direction and branch connections. C. Install underground, double-contained fill and vent piping at uniform slope downward toward fuel oil storage tank D. Install reductions in pipe sizes using eccentric reducer fittings. Install fitting with level side down. E. Install flexible connectors at piping connections to USE. F. Install double—contained piping according to manufacturer’s written instructions for assembly, joining, trench preparation, and installation. ; Set tank on fill materials and install hold-down straps. F. Install piping connections. G. Install tank leak-detection and -monitoring devices. H. Install containment sumps.