Specifications include, but are not limited to:The Work includes furnishing all labor, materials, tools and equipment necessary to repair the Fire Sprinkler Systems at Various Locations. 1. Police Precinct #3 – 2165 St. Stephens Road a. Install a Head Box with head and head wrench b. Pipe 2” drain away from front door c. Dust off loaded sprinkler heads 2. Gulf Coast Exploreum – 65 Government Street a. Replace approximately fifty-five (55) chrome recessed pendent sprinkler heads on 2nd Floor, contractor to confirm b. Replace approximately forty (40) brass uprights in the crawl space, contractor to confirm c. New sprinkler heads will be of the same size, temperature, and rating as existing d. Re-charge existing anti-freeze system 3. West Regional Library – 5555 Grelot Road a. Repair leak on second floor – cut out pipe, replace with new, replace sprinkler head b. Dust off sprinkler heads c. Replace painted sprinkler heads d. Replace missing head wrench in head box e. Install lock on PIV valve 4. Ben May Main Library – 701 Government Street a. Dust off sprinkler heads, replace any that cannot be dusted b. Replace missing heads in head box 5. Fire Station #28 – 7050 Old Military Road a. Repair Leak and Insulate Backflow Preventer 6. Theodore Park – 7171 Old Military Road a. Repair Leak, if needed, and Insulate Backflow Preventer 7. Harmon Park – 1611 Belfast Road a. Replace sprinkler heads in kitchen b. Dust off loaded sprinkler heads