Specifications include, but are not limited to: Unless otherwise indicated, the deliverables will meet or exceed the following specifications and requirements: 1.4.2.1 Load: 1.4.2.1.1 Floor Load: 300 psf. 1.4.2.1.2 Floor Load: 90 psf. Uniform live load while building is being lifted. 1.4.2.1.3 Roof Load: 150 psf. 1.4.2.1.4 Walls: 150 mph. 1.4.2.2 Building size: (Equipment Shelter) 1.4.2.2.1 Outside: Approximately 12ft W x 30ft L x 10ft 6in H; (dimensions +/- 8”). 1.4.2.2.2 Equipment Room: Approximately 10ft 8in W x 20ft 6in L x 9’-0” H (Nominal). 1.4.2.2.3 Generator Room: Approx. 10ft 8in W x 9ft 2in L x 9’-0” H (Nominal). 1.4.2.2.4 Estimated Module Weight: 87,000 lbs. 1.4.2.3 Shell: 1.4.2.3.1 Floor: 6-3/4" solid concrete floor. 1.4.2.3.2 Walls: 4" Solid concrete. 1.4.2.3.3 Roof: Solid concrete 4” at eave and 5” at ridge. Designed to withstand falling ice. Periodic inspection and maintenance required to maximize roof lifespan. 1.4.2.3.4 Design: Step-joint design. 1.4.2.3.5 Tie down: (4) Tie down Plates. 1.4.2.3.6 Bolts: Painted bolts to replace lifting lugs. 1.4.2.3.7 Concrete: 5000 psi lightweight concrete. 1.4.2.3.8 Reinforcing: Steel #4 and #6 bars, 60,000 psi (Grade 60 ASTM-615). 1.4.2.3.9 Ratings: Walls to be 2 hr. fire rated. 1.4.2.3.10 Ballistics: Tested for UL-752, (HPR - 30.06 - point blank range) 1.4.2.4 Exterior Finish: 1.4.2.4.1 Walls: Washed exposed aggregate and sealed. Finish to be brown/earth tone in color. 1.4.2.4.2 Roof: Trowel surface and sealed, broom finish. Color to be white. 1.4.2.5 Interior Finish: 1.4.2.5.1 Floor: Sealed concrete. 1.4.2.5.2 Interior Walls: 1/2" APA Rated OSB covered with a white, fiberglass reinforced plastic (FRP). 1.4.2.5.3 Ceiling: 1/2" APA Rated OSB covered with a white, fiberglass reinforced plastic (FRP). 1.4.2.6 Insulation: 1.4.2.6.1 Interior Partition Wall: R-11 Fiberglass Batt type Insulation. 1.4.2.6.2 Exterior Walls: R-11 Rigid Polyisocyanurate Insulation. 1.4.2.6.3 Ceiling: R-19 Rigid Polyisocyanurate Insulation...