Please note: This is a Sole Source Notification. Specifications include, but are not limited to: Model: 93PM UPS 20-200kW – Or Approved Equal –. Any supplied UPS MUST have the following : 480V in, 480V out (3 wire) System Voltage, 40kW Rated, 50kW Frame Capacity, Standard 97% Efficiency, Firmware expandable to 50kW, Sidecar Bypass Cabinet, MUST Include Power Xpert Gateway Card MUST Include 7x24 Startup, Contractor M UST provide appropriate batteries Acoustical noise: Noise generated by the UPS under normal operation shall not exceed 65dbA at one meter from any operator surface, measured at 25 degrees C (77 degrees F) and full load. MUST be able to isolate battery banks to ensure uptime during required maintenance. System will provide approximately 90 minutes of uptime at approximately 40kw. Comparable product to the Eaton ‘brand’ or Predict Pulse which maintains a wireless remote monitoring that is installed during startup Equipment MUST have Temperature and environmental sensor with analog and networked (email) alarming. Equipment MUST have 24x7 alarm monitoring that can dispatch, report, and provide real-time access to health data for the UPS, Remote alarm monitoring will be monitored by Contractor (to be listed as optional item) System MUST have ability to email notifications to specified JPD/CBJ staff External audible or light alarm for monitoring by staff outside the server room UPS MUST have LTE cellular modem/router hardware capabilities, Contractor MUST have factory-authorized service representative in Juneau to supervise UPS installation, startup, preliminary testing, and adjustment and to participate in final tests and inspection. Additional products that MUST be supplied as part of this Bid include the following : c JPD will coordinate with the awarded Contractor and electrician a timeline for that to take place. JPD requires the Contractor to provide JPD staff with overview and familiarity training including detailed operating instructions covering operation under both normal and abnormal conditions to facilitate trouble reporting. Dimensions & Redundancy for UPS. Maximum footprint size not to exceed 98.4” wide x 42” Deep x 74” Tall.